Daily Usage Report for Ludwell Estates_CE for 07/12/2026

Current Summary Info:30-day Summary Info:
Total number of residents: 55Total number of residents: 55
Total Usage: 4,867Total Usage: 120,480
Total Pumpage: 6,800Total Pumpage: 195,100
Pumpage minus Tenant Usage: 1,933 (28.43% water loss)Pumpage minus Tenant Usage: 74,620 (38.25% water loss)
Average Usage per Resident per Day: 88Average Usage per Resident per Day: 73
  
Last read date as of this report: 07/11/2026Last read date as of this summary: 06/21/2026
Current read date as of this report: 07/12/2026Current read date as of this summary: 07/12/2026
Average number of days this report covers: 1 (Min: 1, Max: 21)Average number of days this summary covers: 30 (Min: 15, Max: 30)

Pumpage

These meters are reporting water flow into the facility.

Acct #Tx IDCurrent
Read
30-Day
Old Read
30-Day
Pumpage
30 Day
Average
Current
Read
Previous
Read
Daily Use
Master Meter 217022417000224800192,2006,4074170004102006,800
Master Meter 3239562086002057002,900972086002086000

Total: 2 out of 60 (3.33%)
Total 2-day pumpage: 6,800
Total 30-day pumpage: 195,100

No Reads Data

Sometimes transponders will send out data without reading information. This sometimes happens for a few days with newly configured Hexagram transponders. If this condition persists for more than a few days, then they should be rewired or reconfigured.

Acct #Tx IDCurrent
Read
30-Day
Old Read
30-Day
Usage
30 Day
Average
Current
Read
Previous
Read
Daily Use
2ENo Meter       
16WNo Water       
18WSewer       

Total: 3 out of 60 (5.00%)

Meter Not Advancing

These meters haven't registered any usage in a while, which may mean that either the lot is unoccupied, the residents have moved out temporarily, or the meter chamber is stuck with sand or rust. For Cereniti equipped systems, this could also mean the radio is disconnected from the meter.

Acct #Tx IDCurrent
Read
30-Day
Old Read
30-Day
Usage
30 Day
Average
Current
Read
Previous
Read
Daily Use
7E592931300130000130013000
14E59282106970106970001069701069700
15E59214103500103500001035001035000
17E593241490149000149014900
25E6410884650846500084650846500
1W5925914810148100014810148100
31W5935124630246300024630246300
33W592176170617000617061700

Total: 8 out of 60 (13.33%)

High Users of Water

A resident is considered a high user if their 1-day usage is 250% higher than their per-day 30-day average and their 1-day usage is more than 100 gallons, or their 1-day usage is 300 gallons or more.

Acct #Tx IDCurrent
Read
30-Day
Old Read
30-Day
Usage
30 Day
Average
Current
Read
Previous
Read
Daily UsePercent Of
Total Usage
12E5931612750107901,9606512750125701803.70%
19E592271010408361017,43058110104099310865 (2 days)17.77%
23E592571714401634607,9802661714401710903507.19%
29E5931270650688101,8406170650701904609.45%

Total: 4 out of 60 (6.67%)
Total usage: 1,855 out of 4,867 (38.11%)

Backward Running Meters

A meter is running backwards when the last read shows a higher reading than the current read.

Acct #Tx IDCurrent
Read
30-Day
Old Read
30-Day
Usage
30 Day
Average
Current
Read
Previous
Read
Daily UseMonth Old
Read
16E Test642402001000800 (15 days)532002000 (last read 144 days ago)10

Total: 1 out of 60 (1.67%)

No Transmissions Received In A While

If a transponder has not transmitted a reading for more than 3 days, then the read shows up here. It is recommeded that you check the transmitter to make sure it is not lying on the ground, broken, missing, or water-logged.

Acct #Tx IDCurrent
Read
30-Day
Old Read
30-Day
Usage
30 Day
Average
Current
Read
Previous
Read
Daily UseDate Of
Last Read
16E Test642402001000800 (15 days)532002000 (last read 144 days ago)02/18/2026
30E592651173401159001,4404811734011728060 (last read 53 days ago)05/20/2026
32W593033896038610350 (28 days)12389603890020 (3 days) (last read 57 days ago)05/16/2026
34W5929286700867000086700867000 (21 days) (last read 30 days ago)06/12/2026

Total: 4 out of 60 (6.67%)

Usage Report

Acct #Tx IDCurrent
Read
30-Day
Old Read
30-Day
Usage
30 Day
Average
Current
Read
Previous
Read
Daily Use
Master Meter 217022417000224800192,2006,4074170004102006,800
Master Meter 3239562086002057002,900972086002086000
2ENo Meter       
3E23959902070290900
4E2394040190372202,970994019040090100
5E59253447404387087029447404471030
6E592912590402515007,540251259040258820220
7E592931300130000130013000
8E59260446504377088029446504461040
9E593131156401137301,9106411564011556080
10E59249329703212085028329703296010
11E5922865360635001,86062653606530060
12E5931612750107901,960651275012570180
14E59282106970106970001069701069700
15E59214103500103500001035001035000
15E Test64233290010001,90063290029000
16E5925559070576101,46049590705903040
16E Test642402001000800 (15 days)532002000 (last read 144 days ago)
17E593241490149000149014900
18E5934990120877202,400809012089980140
19E592271010408361017,43058110104099310865 (2 days)
20E5932662600593003,3001106260062490110
21E5924216900137403,160105169001682080
22E593311187501149303,820127118750118490260
23E592571714401634607,980266171440171090350
24E59248963009623070296300963000
25E6410884650846500084650846500
27E593411217401190202,720911217401217400
28E592561294201247504,670156129420129270150
29E5931270650688101,840617065070190460
30E592651173401159001,4404811734011728060 (last read 53 days ago)
31E5933243180405102,670894318042900140 (2 days)
Farm5929084190829201,27042841908417020
1W5925914810148100014810148100
3W2394228580260702,51084285802850080
4W5927642340422001405423404232020
6W5930169890686401,2504269890698900
7W59309346403401063021346403461030
11W5923373910713902,520847391073800110
12W5933095560936601,90063955609551050
13W593041795601750404,520151179560179440120
14W592361346101319802,63088134610134510100
15W592231755601707704,790160175560175400160
16WNo Water       
17W593391145601117302,83094114560114440120
18WSewer       
19W5931844270381206,1502054427044010260
20W5707934570329301,64055345703456010 (last read 1 day ago)
21W5924648740466202,12071487404869050
22W5924734820343704501534820348200
23W592051598601553404,52015115986015977090
24W59310376803727041014376803765030
25W59286308603009077026308603083030
29W592741436501408102,84095143650143530120
30W5928740910393701,54051409104089020
31W5935124630246300024630246300
32W593033896038610350 (28 days)12389603890020 (3 days) (last read 57 days ago)
33W592176170617000617061700
34W5929286700867000086700867000 (21 days) (last read 30 days ago)
35W592192011201984002,720 (19 days)143201120200460132 (5 days) (last read 1 day ago)

NOTE: The tooltip rendering is done using the truly amazing BoxOver, which can be found at http://boxover.swazz.org/